Voltage Drop Calculator - Wire Size & Circuit Analysis

Voltage Drop Calculator

Amps

Enter circuit parameters and click Calculate

Choose from NEC data, estimated resistance, or custom impedance

Understanding Voltage Drop in Electrical Circuits

Quick Summary: Calculate voltage drop for any electrical circuit with our free calculator. Supports single-phase and three-phase systems, copper and aluminum conductors, and provides NEC compliance checking. Essential for electricians, engineers, and electrical contractors.

What is Voltage Drop?

Voltage drop is the reduction in electrical potential (voltage) as current flows through conductors from source to load. All electrical conductors have resistance, and when current flows, energy is lost as heat according to Ohm's Law: V = I × R. This lost voltage means less voltage is available at the load, potentially causing equipment underperformance, energy waste, and safety concerns.

Example: A 120V circuit with 5V voltage drop delivers only 115V to the load—a 4.17% reduction. For sensitive equipment or motors, this reduced voltage significantly impacts performance and efficiency. The National Electrical Code (NEC) provides guidelines to limit voltage drop and ensure proper equipment operation.

Basic Voltage Drop Formulas

Single-Phase: Vdrop = 2 × I × R × L

Where: I = current (A), R = resistance (Ω per unit length), L = one-way length

Factor of 2 accounts for both conductors (hot and neutral)

Three-Phase: Vdrop = √3 × I × R × L × PF

Where: √3 ≈ 1.732, PF = power factor (typically 0.7-1.0)

Applied to line-to-line voltage for balanced loads

NEC Voltage Drop Standards

The National Electrical Code (NEC) provides voltage drop recommendations in Articles 210.19(A) for branch circuits and 215.2(A)(1) for feeders. While not strict requirements for most applications, these guidelines ensure optimal system performance:

Circuit TypeRecommended MaxPerformance Impact
Excellent (≤2%)≤2%Optimal performance, minimal efficiency loss
Good (Branch Circuit)≤3%NEC recommended for branch circuits
Warning (Total)≤5%NEC maximum (feeder + branch combined)
Critical>5%Exceeds NEC guidelines, likely problems

Special considerations: Critical loads (life safety, emergency systems, data centers) often require stricter limits of 1-2%. European standards (IEC 60364-5-52) typically allow 3% for lighting circuits and 5% for other uses. Always consult local electrical codes and project specifications for specific requirements.

Wire Gauge and Resistance

Wire gauge (AWG - American Wire Gauge) inversely relates to wire diameter: smaller AWG numbers indicate larger wire with lower resistance. Each 3-step increase in AWG approximately doubles resistance. Wire resistance depends on material (copper or aluminum), temperature, and cross-sectional area.

AWGmm²Copper (Ω/1000ft)Aluminum (Ω/1000ft)Typical Use
142.083.075.0615A circuits, lighting
123.311.933.1820A circuits, receptacles
105.261.211.9930A circuits, dryers, AC
88.370.7641.2640-50A, ranges, heat pumps
613.30.4910.80855-65A, sub-panels
421.20.3080.50870-85A feeders
233.60.1940.31995-115A feeders
1/053.50.1220.201150A service entrance
4/01070.06080.100200A+ service

Note: Resistance values shown are at 75°C (167°F), which is standard for insulated conductors in conduit. Temperature affects resistance: copper increases approximately 0.4% per °C above 20°C reference temperature.

Copper vs Aluminum Conductors

Copper Advantages

  • Lower resistance (better conductivity)
  • More ductile and easier to work with
  • Less expansion/contraction with temperature
  • Standard termination methods
  • Longer service life in most applications
  • Smaller wire size for same ampacity

Aluminum Advantages

  • Lower material cost (30-50% savings)
  • Lighter weight (70% less than copper)
  • Easier to handle for large sizes
  • Good for overhead and long runs
  • Common for service entrance conductors
  • Abundant and sustainable resource

Aluminum considerations: Requires special treatment due to higher resistance and tendency to oxidize. Use aluminum-rated devices (marked AL or CU-AL), apply anti-oxidant compound at terminations, and upsize by two AWG gauges compared to copper (use 10 AWG aluminum instead of 12 AWG copper). NEC Article 310.106 prohibits aluminum smaller than 12 AWG for residential branch circuits. Proper installation is critical to prevent loose connections and fire hazards.

Practical Calculation Examples

Example 1: Residential 120V Circuit

Scenario: 15A lighting circuit, 120V, 80 feet to farthest fixture, 14 AWG copper wire

Calculation:

  • Resistance: 14 AWG copper = 3.07 Ω per 1000 ft
  • Round-trip resistance: (3.07 ÷ 1000) × 80 × 2 = 0.491 Ω
  • Voltage drop: 15A × 0.491Ω = 7.37V
  • Percentage: (7.37V ÷ 120V) × 100% = 6.14%

Result: Critical! Exceeds 5% NEC maximum. Upgrade to 12 AWG (3.7%) or 10 AWG (2.3%).

Example 2: Three-Phase Motor Circuit

Scenario: 50HP motor at 480V 3-phase, 200 feet, power factor 0.85, 8 AWG copper

Calculation:

  • Motor current: 50HP × 746W/HP ÷ (1.732 × 480V × 0.85) = 52.8A
  • Resistance: (0.764 ÷ 1000) × 200 × 2 = 0.306Ω
  • Voltage drop: 1.732 × 52.8A × 0.306Ω × 0.85 = 23.8V
  • Percentage: (23.8V ÷ 480V) × 100% = 4.96%

Result: Warning - just under 5% maximum. Consider 6 AWG (3.1%) for better motor performance.

Consequences of Excessive Voltage Drop

  • Motors: Reduced torque, lower speed, overheating, higher current draw, shortened lifespan. 5% voltage drop can increase motor current by 10-15%.
  • Lighting: Noticeable dimming, reduced light output, possible flickering, shorter bulb life. Incandescent lights are particularly sensitive.
  • Electronics: Malfunction, improper operation, reduced performance, potential damage to sensitive equipment.
  • Heating elements: Reduced heat output proportional to voltage squared (5% voltage drop = 10% heat reduction).
  • Energy waste: Power loss in conductors as heat: Ploss = I² × R. This represents wasted energy and increased operating costs.
  • Safety concerns: Overheating conductors, inadequate operation of protective devices, fire risk from undersized wiring.

Solutions to Reduce Voltage Drop

1. Increase Wire Size

Most common solution. Larger wire has lower resistance. Increasing by one AWG gauge reduces voltage drop by approximately 20-25%. Balance initial cost against long-term energy savings and performance benefits.

2. Reduce Circuit Length

Relocate power source closer to load, eliminate unnecessary bends or indirect routing. Each 10% reduction in length provides 10% reduction in voltage drop. Consider multiple branch circuits instead of one long run.

3. Increase System Voltage

For same power, higher voltage means lower current, reducing voltage drop. 240V single-phase has half the current of 120V for same load. 480V three-phase is standard for large motors and industrial equipment.

4. Use Copper Instead of Aluminum

Copper has 39% lower resistance than aluminum for same size. However, copper costs more. For new installations, copper is often worth the premium for better performance and easier installation.

5. Split the Load

Divide large loads across multiple circuits. Each circuit carries less current, reducing voltage drop. Also provides redundancy and better load balancing.

Additional Resources

For more information on voltage drop and electrical code requirements: